====== Renewable Energy Generation Overview ====== The building renewables consist of two main plants - a renewable energy plant and a co-generation plant. A part of the co-gen plant (the ORC turbine) provides input for the renewable energy plant. Please see the other knowledgebase sections for further details on each aspect of the system. ===== Co-Generation Plant ===== {{ :diagram:cogen_overview.png?300 |}} Water is heating to approximately 200°C by 4x solar thermal collectors on the roof, that hot water is harnessed by the following systems (in cascading order) with the output water still being potable. * 180°C: Organic Rankine cycle Turbine. Max 10kW * 120°C: Evaporative Chiller: Cooling 19kW, Heating 60kW. * 60°C: Augment Building Hot Water Supply ===== Renewable Energy Plant ===== {{ :diagram:renewables_overview.png?300 |}} ==== Inputs ==== * Photovoltaic Cells. 20kWp * Organic Rankine cycle (ORC) turbine output from Co-Gen Plant. Max 10kW * Wind Turbine: Max 12kW * Hydrogen Fuel Cell: Max 10kW ==== Outputs ==== * Power stored in 2x 50kWh flow-technology batteries. * Energy output to Building Microgrid (microgrid is not connected to the building main grid)